31
MicroSCADA Pro supports Intel x86 compatible processors and Microsoft’s x32
(32-bit) compatible operating systems: Windows XP, Windows 2000 Server and
Windows Server 2003. For information on requirements, refer to Installation and
Administration Manual.
MicroSCADA Pro can be installed as part of Windows domain, but it cannot be
installed to the domain server. A Windows Domain is a logical grouping of
computers that share common security and user account information. This
information is stored in a master directory database (SAM) which resides on a
Windows server designated as a domain controller.
We recommend to use MicroSCADA in a stand-alone server to avoid complicated
errors.
It is possible to run 32-bit programs on Intel x64 architecture
processors.
3.1.2. Systems (SYS)
Create a SYS:B object with at least the following attributes (see the example in
Fig. 3.1.3.-1):
Table 3.1.2.-1 Mandatory attributes
ND The node number of the base system. The node number must be
unique within the entire MicroSCADA Pro network, see .
SA The MicroPROTOCOL station address of the base system. Like the
node number, the station address must be unique within the
network, see .
The following attributes are optional:
Table 3.1.2.-2 Optional attributes
ER The use of the base system as a routing node. It means that if
routing is enabled in a specific base system, it can route messages
addressed to other nodes. Refer to the System Objects manual.
DN, DS The default node number and default station type. These attributes
should not be used.
SH Shadowing attribute. This attribute is used for the configuration of
hot stand-by, see 3.8. Configuring redundancy.
TI Timeout length for node communication. The attribute can be locally
and temporarily sidestepped by a SCIL function (TIMEOUT).
PC, RC Memory cache space attributes, see ‘Tuning memory parameters’ in
this section.
FS File Sync. The flushing of buffered data on to a disk.
DE Allowing applications in the base system to be accessed by other
software using DDE.
AA The use of standard audio-visual alarm unit.
CA, CF, CL, TZ Attributes related to an external clock. Refer to the System Objects
manual.