3.8.2.1. Configuring IEC 61850 OPC Server
In a hot stand-by system, the IEC 61850 OPC Servers should be active both in a
primary (including hot application) and a stand-by (including shadowing
application) computer. This enables that data coming from IEC 61850 process
devices is stored into buffers of the both IEC 61850 OPC Servers all the time.
3.8.2.2. Configuring IEC 61850 OPC Client
In the SYS_BASCON.COM you need a node definition for a IEC 61850 OPC
Client
; IEC61850 OPC_Client_Nod_begin
#CREATE NOD:V ;Client node
#SET NOD:VLI = 1 ;Client Link number
@NODE = 8 ;Node number
#SET NOD:VSA = 208 ;Node address
#SET NOD:VNN = "HSB1" ;Name of the base system
#SET NOD:VDI = 10 ;Diagnostic interval
#SET NOD:VDT = 30 ;Diagnostic timeout
#CREATE NOD'NODE':B = %NOD ;Creating node; IEC61850 OPC_CLIENT_Nod_end
For the creation of stations include this in the SYS_BASCON.COM file
#CREATE STA:V = LIST(-
TT = "EXTERNAL",-
ST = "SPA",-
TR = "UTC",-
ND = 8,-
TN = 60)
#CREATE STA60:B = %STA
3.8.2.3. Configuring External OPC Data Access Client
A051618
Fig. 3.8.2.3.-1 Setting of the client communication parameters
In this configuration set the stations in use. Use Enable Circular Buffering' in the
OPC Configuration Tool.
MicroSCADA Pro
System Configuration
Configuration Manual
SYS 600 9.2SYS 600 9.2
1MRS756112