communication route is in good condition. The communication is switched from the
main line to the back-up line and vice versa if the active line is detected to be
broken. The line switch is always initiated by the master.
Redundant
RP570 slave
COM500i
NCC
Fig. 3.8.4.-1 Redundant RP570 slave
System configuration tool supports the configuration of the redundant RP570 slave.
By creating a RP570 slave line and pressing the Add redundancy menu item, the
back-up line is created and the same SPI station object can be connected to two
lines.
If the system configuration tool is not used, the following steps should be taken to
configure a redundant RP570 slave line.
1. Define the main line.
2. Define the back-up line.
3. Define the station.
In order to operate as a redundant pair of lines, the main line and the back-up line
must be explicitly configured using the line attributes LI and RU. For more details,
refer to the Chapter Redundant line attributes in the System Objects manual, SPI
station description.
3.8.5. Configuring redundant IEC 60870-5-101 slaves
The IEC 60870-5-101 slave protocol in PC_NET also provides a possibility for
redundancy which follows the corresponding IEC 60870-5-101 standard. In
practice, this means that one IEC slave station object is connected to two IEC
60870-5-101 slave lines controlling two serial ports. One of these is treated as the
main line and the data transfer takes place using this line. The other line is the back-
up line which is activated if the main line fails. If a communication disturbance is
110
SYS 600 9.2SYS 600 9.2
MicroSCADA Pro
System Configuration
Configuration Manual
1MRS756112